Fluid |
Gas and oil |
Repeatability |
±1.0 % of adjustable range |
Adjustable range (mbar, kPa, bar, MPa) |
0.3 kPa to 15 MPa -0.1 ~ -0.15 bar to 15 MPa |
Dead band |
Fixed One SPDT : Approx. 5 % adjustable range Two SPDT : Approx. 10 % of adjustable range |
Working temperature |
Ambient : -40 ~ 65 °C Fluid : Max. 100 °C |
Degree of protection |
EN60529/IEC529/IP65 |
Pressure connection |
Stainless steel (316SS) 316L SS, Monel and Hastelloy-C |
Element |
Stainless steel (316L SS) Monel, Hastelloy-C Viton (Up to 4 kPa adjustable range) |
Case and cover |
ALDC 12.1 Silver gray finished aluminium |
Process connection |
¼", ⅜", ½" PT, NPT and PF |
Contact |
Micro contact type One SPDT (P953-1B3) Two SPDT (P953-2B3)(Only available with single setpoint) |
Contact rating |
SPDT contact rating AC 125 V / 250 V, 15 A DC 125 V, 0.4 A for resistance load DC 125V, 0.03 A for inductive load |
Conduit connection |
¾" NPT (F) |
Certificates |
KCS Ex d IIC T6 ATEX II 2G Ex d IIC T6 Gb IECEx Ex d IIC T6 Gb |